Model: CNG310 10-100KVA(3Ph/1Ph)
Nominal Input Voltage: 380/400/415VAC
Efficiency: 96%
Output Power Factor: 0.8/0.9
Parallel: Maximum 6 PCS UPS
Battery can be shared in parallel mode

Application field:

  • IDC
  • Hospital
  • Traffic control field
  • Bank, Securities Clearing Center
  • Control applications in industrial processes
  • Medium-scale network management system, billing center

Description

CNG310 series low frequency online UPS is manufactured by CONSNANT, covering rated capacities of 10KVA-100KVA. It adopts double-conversion online VFI topology with built-in output isolation transformer, SCR thyristor rectifier and IGBT inverter. Designed for mission-critical loads including IDC data centers, hospitals, banking & securities clearing centers, traffic control systems and industrial process control equipment, this series features outstanding anti-interference, overload and shock resistance performance. It delivers clean, low-noise sine-wave power and supports standalone operation or parallel redundant expansion for high-reliability power supply systems.

Key Features

1. Double Conversion Topology with Output Isolation Transformer for Superior Power Quality

Continuous inverter power supply under online mode, with built-in EMI input & output filters. The low-frequency isolation transformer eliminates mains surge, harmonic interference and high-frequency zero-line noise, greatly reducing zero-ground voltage to secure stable operation of medical instruments and network devices. Built-in back-feed protection prevents reverse energy damage to municipal power grid. Full microprocessor digital control equips static automatic bypass and manual maintenance bypass for zero-break switching during faults or maintenance.

2. Ultra-Low Input Harmonics to Cut Distribution & Generator Investment

Standard sinusoidal harmonic absorption filter restricts input current THDi below 5%, input power factor ≥0.92. The low distortion remains stable regardless of grid impedance and load types, avoiding resonance with power capacitor banks. It allows smaller sizing of upstream distribution transformers and diesel generators, saving overall power system cost. Separate rectifier and bypass power input is supported for dual independent AC power sources without extra galvanic isolation.

3. Intelligent Full-Range Battery Management to Extend Battery Lifespan

Multi-protection battery system including deep discharge cut-off, temperature-compensated charging, automatic & manual battery test functions. Standard 384VDC DC bus voltage compatible with VRLA AGM, gel and NiCd batteries. Controlled charging current and AC ripple voltage less than 1% slow down battery aging; external battery cabinets can be connected to extend backup runtime to several hours.

4. Strong Overload & Shock Load Compatibility

0.9 output power factor perfectly matches ICT and industrial loads; 3:1 crest factor adapts to lighting, motor and other impulse loads. Tiered overload protection: 110% rated load for 5 hours, 125% for 10 minutes, 150% for 1 minute. High short-circuit withstand capacity ensures compatibility with all kinds of industrial transformer loads.

5. Parallel Redundancy & Flexible Capacity Expansion

Up to 6 units can be connected in closed-loop parallel for N+1 redundancy. The parallel system keeps stable operation even if one communication cable is disconnected. Users can add extra UPS units anytime to expand power capacity without upfront over-investment. Economy mode boosts system efficiency up to 98% to reduce energy consumption under stable mains conditions.

6. Comprehensive Monitoring & Multi-Protocol Communication Interfaces

Multi-language color LCD touch panel stores 128 event logs to display real-time voltage, current, alarms and working status. Hardware interfaces include dual RS232 ports, RS485, SNMP expansion slot and EPO emergency power off terminal. Standard Watch & Save 3000 monitoring & shutdown software supports Windows, Linux, Mac OS X and all mainstream Unix systems; TeleNetGuard remote maintenance system enables global real-time monitoring with plug-and-play PC connection. Generator interface automatically adapts to frequency & phase deviation of diesel generators and optimizes battery charging logic.

7. Wide Installation Adaptability & Reliable Protection

Rectifier input does not require neutral wire to fit all standard 3-phase distribution systems. Independent input, bypass, output and maintenance breakers plus battery fuse are pre-installed, with copper bus terminals for high-current wiring. IP20 protection degree, operating temperature range 0℃ ~ +40℃, relative humidity ≤95% non-condensing, noise ≤65dBA at 1m. Black integrated metal cabinet with rigid industrial structure.

Product Structure:

Low Frequency Online UPS

 

Working Diagram:

Low Frequency Online UPS

 

Typical Application Fields:

IDC data rooms, general & specialized hospitals (emergency, lab, medical imaging equipment), banking & securities settlement centers, traffic tunnels & rail transit control, industrial automation production lines, government billing centers, campus computer rooms, police stations, power grid dispatching stations, mobile container hospitals and other critical power supply scenarios.

Product service:

1. Pre-sales consultation; After-sales worry-free.

2. Support ODM and OEM.

3. Online guidance and Technical support.

Technical Parameters:

Model CNG310 10KVA CNG310 15KVA CNG310 20KVA CNG310 30KVA CNG310 40KVA CNG310 60KVA CNG310 80KVA CNG310 100KVA
Capacity 8KW/9KW 12KW/13.5KW 16KW/18KW 24KW/27KW 32KW/36KW 48KW/54KW 64KW/72KW 80KW/90KW
Input
Rated voltage 380/400/415 Vac three-phase
Voltage range ±20%
Frequency range 45-65Hz
Range(HZ) 50±5%(±10%)Bypass synchronization tracking
Rectifying pulse number 6 pulse rectification
Phase system 3φ4W+PE(Three phase five wire system)
Battery voltage(VDC) 384
Battery quantity(section) Standard with 32knots(30~34knots, can be set through the LCD panel)
Standard 40 knots(38~42 knots, can be set by LCD panel)
Output
Power factor 0.8/0.9
Voltage(V) L-N:220±1%
Voltage Regulation <1%(online and battery mode) at 100% linear load,<2% allow 100% imbalance
Frequency(Hz) Normal power, tracking the frequency of power, Frid abnormal.50+0.2%
Transfer Time(ms) 0
Recovery Time Dynamic load voltage transient <5%, recovery within 5ms
Waveform Distortion Linear load THD 3%: Nonlinear load THD 5%
Overload Capacity 125% full load for 10 minutes, maintain 150% full load for 1 minute and then switch to bypass power supply,after reducing the load can automatically restore the inverter
Crest Factor 3:1
System
Communication Function Provides dry contract communication and RS232/RS485, Optional SNMP option to achieve intelligent monitoring
of UPS
Panel Display LED displays working status and fault indication: LCD displays three-phase input voltage, input frequency,output voltage, load, battery boltage, battery charge and discharge current, etc
Display LCD 7′ touch screen display
The Audio Noise(dB) <65(within 1 meter)
Alarm Function Battery low voltage, abnormal power supply, overload, UPS failure, over termperature protection
Protection Input over voltage, battery under voltage, overload, short circuit, over temperature protection
Cooling Way Forced cooling
Operating Temperature(°C) -10 ~ 35 without de-rating
Humidity 0~95%, non condensing
Max Altitude Rated power at 1000m,(increase 100m and decrease by -1%), maximum 4000m
Protection level IP21
Dimensions:(WxDxH)mm 540*657*1132 555*725*1290 800*745*1700
Weight(KG)N.W 173 199 211 254 306 385 390 665
Weight(KG)G.W 196 222 233 276 329 415 419 724

 

What is Low Frequency Online UPS?
Low frequency online UPS adopts traditional analog circuit design, consisting of SCR thyristor rectifier, IGBT inverter, bypass circuit and power frequency step-up isolation transformer. Its rectifier and transformer operate at 50Hz, hence the name low frequency UPS. It applies VFI double-conversion online topology, with the inverter continuously powering loads. The output isolation transformer provides complete galvanic isolation and superior anti-surge & anti-interference performance.
What are the core differences between low-frequency UPS and high-frequency UPS?
1.Structure: Low-frequency UPS integrates built-in output isolation transformer; high-frequency UPS has no isolation transformer and relies on high-frequency switching devices for voltage boost. EMI performance: High-frequency UPS generates high-frequency harmonic current on neutral wire with high neutral-ground noise voltage; low-frequency UPS delivers much lower zero-ground voltage without high-frequency clutter, ideal for medical and precision network equipment. Load adaptability: Low-frequency UPS features stronger overload, impulse and short-circuit withstand capacity for motors and industrial surge loads; high-frequency models only suit standard light IT loads. Dimension & weight: Low-frequency UPS is bulky and heavy; high-frequency UPS is compact, lightweight with lower unit price. Application: Low-frequency for IDC, hospitals, industrial and financial high-reliability sites; high-frequency for small office single-point equipment.
Does the UPS support parallel expansion? What is the maximum parallel quantity?
Closed-loop parallel function supports up to 8 units of the same series for N+1 redundancy. The parallel system remains stable even if one communication cable is disconnected. Users can add extra UPS units anytime to expand capacity without over-investment in advance. Max efficiency reaches 98% under Economy Mode.
How to extend UPS backup runtime?
Connect multiple external battery cabinets to expand backup duration by increasing battery capacity. The unit integrates temperature-compensated charging, deep discharge protection, auto & manual battery test functions to reduce battery loss.
Why backup runtime is much shorter than before?
1.Aging batteries, damaged single cell, leakage or bulging; Excessively high actual load rate; Abnormal battery charging circuit with insufficient charging. Solutions: Test battery voltage, replace aged batteries, reduce load, inspect charging module.

Related products

12
CNS-L1208 Series 12V Lithium lon Iron Phosphate Battery(LiFePO4)
3
CNS-LFP12V Series Lead Acid Replacement Battery ( LiFePO4 )
2
CNS-LFP24V Series Lead Acid Replacement Battery ( LiFePO4 )
2
CNS-LFP36V Series Lead Acid Replacement Battery ( LiFePO4 )

Related Articles

-2023
Shenzhen CONSNANT Technology Co., Ltd. team building activities Huizhou trip.
-12025
CONSNANT 10th Anniversary Celebration
-2024
CONSNANT Team Building & Annual Meeting Activities

Contact us

Partner with CONSNANT to find the perfect power system for your business. Our technical team is ready to provide customized solutions to optimize power usage and maximize efficiency.

Solution5 1