products

Communication Power Rectifier Module Communication Power Rectifier Module (3) Communication Power Rectifier Module (2)

Communication Power Rectifier Module

share

Facebook
LinkedIn

High voltage rectifier module
Model: TR-4830/50/75
Capacity:30A/ 50A / 75A
Output: 42-58Vdc
30A  Input: 85-300Vac  Efficiency: 92% or 93%
50A  Input: 85-300Vac or 120-400Vdc  Efficiency: 95% or 96%
75A  Input: 85-300Vac   Efficiency: 96.6%

Parameter Specification
Item No : TR-4830/50/75
Order(MOQ) : 10 pcs
Payment : T/T
Product Origin : China
Color : Silver
Shipping Port : Shenzhen
Lead Time : 3-7 days
Weight : ≤2 Kg

 

Protection:

  • Output short circuit protection
  • Output overvoltage protection
  • Output undervoltage warning
  • Input overvoltage alarm and protection
  • Input undervoltage alarm and protection
  • Over-temperature protection

Technical Parameters:

Model TR-4830 TR-4850 TR-4875
Capacity 30A 50A 75A
Input
Input voltage 85Vac ~ 300Vac (Single-phase 2-wire) 85Vac ~ 300Vac 85Vac ~ 300Vac(Single-phase two-wire)
Rated Input voltage 110Vac/220Vac
Nominal input 100Vac ~ 120Vac 200Vac ~ 250Vac 100Vac ~120Vac
200Vac ~ 240Vac 200Vac ~240Vac
Frequency range 45Hz-66Hz
Max. input current 12A 20A ≤26A
Surge current Meet standards:ETSI300132-3 Meet standards: EN/IEC61000-4-5 Meet standards: ETSI300132-3
Efficiency ≥92% @ 220Vac at 50%~100% Load; Typical value: 94% @ 230Vac ≥96.6%@peak value
≥93% @ peak value
Power factor ≥0.95@220Vac,30A ≥0.975@220Vac,50Hz/30%~50% Load ≥0.99@220Vac20-100% Load
≥0.99@220Vac,50Hz/50%~100%Load
Input current THD <10%@220Vac,20%~100% Load <5%@ 50% Load,220Vac,50Hz <3% @≥50% Load
<12%@ 30% Load,220Vac,50Hz <8% @≥20% Load
Leakage current <3.5mA@264Vac
Rated power 1766W(176Vac~300Vac) and automatic derating 3000W(176Vac~290Vac) 4000W(176ac~300Vac)
depending on the internal temperature rise 1250W(85Vac~175Vac linear derating) 1600W-4000 linear (85Vac~176Vac)
of the powersupply, derate to 1605W the minimum.
800W(85Vac~175Vac).
Input fuse Input fuse 15A Input fuse 15A L/N online fuse 30A
Max. input voltage 320Vac (Power supply cannot be damaged)
Output
Output voltage +53.5Vdc
Output voltage setting value +53.5±0.1Vdc
Adjustable range of output voltage +42Vdc~+58Vdc
Current imbalance ≤+3%
Source effect ±0.1%
Load effect ±0.5%
Voltage stabilization accuracy ±0.6%
Minimum current 0A
Rated current 30A 50A 75A
Peak current 33A 53A@53.5V 80A
Temperature coefficient (1/ ℃) ≤±0.02%
Ripple and noise ( peak-to-peak ) 200mVp-p@25 ℃
Environment
Temperature  -40 ℃ ~ +75 ℃
Humidity  5%~95% (non-condensing)
Altitude 0~4000M,to3000m As a basis, every 200 degree increase in altitudem , the maximum temperature of the specification is reduced by 1 ℃
Physical
Weight <1.5kg <2kg <2.1kg
Dimension(W x D x H)mm 97*230.5*41.5 106.5*286*41.5 106.5*2

Related products

IP56 Outdoor Industrial UPS 6 10KVA with cabinet air conditioner1
IP56 Outdoor Industrial UPS 6-10KVA with cabinet air conditioner
Three Phase Output Industrial Online UPS 160 300KVA
Three Phase Output Industrial Online UPS 160-300KVA
consnant.com ip55 floor mount outdoor ups 1 10kva with vrla battery1
IP55 floor mount outdoor UPS 1-10KVA with VRLA battery
Three Phase Output Industrial Online UPS 100 120KVA (5)
Three Phase Output Industrial Online UPS 100-120KVA

Related Articles

NEWS 3
Shenzhen CONSNANT Technology Co., Ltd. team building activities Huizhou trip.
NEWS 2
CONSNANT 10th Anniversary Celebration
NEWS 1
CONSNANT Team Building & Annual Meeting Activities

Contact us

Partner with CONSNANT to find the perfect power system for your business. Our technical team is ready to provide customized solutions to optimize power usage and maximize efficiency.

Solution5 1