SPECIFICATION:

Model Number:TRSS-48300

System capacity:9U300A

Solar Charge Controller Module:
Input voltage range: 120~425V
Output voltage:-54.5Vdc
Output current: 300A (MAX)
Output capacity: 18KW (MAX)
Solar module quantity: 1~6pcs
Rectifier modules:
Input voltage range: 176~300V
Output voltage:-53.5Vdc
Output current: 300A (MAX)
Output capacity: 18KW (MAX)
Solar module quantity: 1~6pcs

CONFIGURATION:
AC input: MCB 63A / 3P * 1, UK35 * 1
PV input: MCB 25A / 2P * 6, DC-SPD * 6
Battery access: MCB 125A / 1P * 3
Primary load disconnect: MCB 125A/1P*3, 63A/1P*3
Primary load disconnect is controlled by a 400A contactor (normally closed)
Configuration: AC Class C 3 + 1 mode 20 KA / 40 KA SPD * 1, DC output lightning protection: Class C DC SPD * 1

Note: above configurations can be customized.

Application field:
Telecom;
Data center

Parameter Specification
Item No : TRSS-48300
Order(MOQ) : 1 pcs
Payment : T/T
Product Origin : China
Color : Black
Shipping Port : Shenzhen
Lead Time : 1-2 weeks
Weight : 37 Kg

Embedded Hybrid Power Supply 48V 300A

Description

TRSS-48300 embedded power supply is a new generation of highly reliable and high-performance hybrid energy system designed by the company based on years of development and online operation experience. The system configuration supports 1-6 hot-swappable rectifier modules and 1-6 photovoltaic modules. The system monitoring module has battery management function and power supply system monitoring function. Appropriately configured sensors can realize environmental monitoring, and provide multiple sets of backup monitoring quantities. It can provide RS485 communication interface to facilitate remote monitoring and unattended operation.
This embedded power supply is mainly used in outdoor cabinets.

Main product specifications

Input voltage range Output voltage Output(MAX) Output maximum power Configuration quantity
Rectifier module 176~300Vac -53.5V d c 300A 18KW 6
Solar Charge Controller Module 120~425Vdc -54.5V d c 300A 18KW 6
Configure
AC input: MCB 63A / 3P * 1, UK35 * 1
PV input: MCB 25A / 2P * 6, DC-SPD * 6
Battery access: MCB 125A / 1P * 3 Specific configuration: it can be customized according to the customer
Primary load disconnect: MCB 125A/1P*3, 63A/1P*3
Primary load disconnect is controlled by a 400A contactor (normally closed)
Configuration: AC Class C 3 + 1 mode 20 KA / 40 KA SPD * 1, DC output lightning protection: Class C DC SPD * 1

 

Principle introduction

The principle of TRSS-48300 embedded power supply system is as follows:

 

Embedded Hybrid Power Supply 48V 300A

The system is powered by three-phase AC mains power through the AC input circuit breaker, all the way to supply power to the rectifier module; at the same time, the three-phase samples are sent to the monitoring board for AC voltage detection. After the output of the rectifier module is combined, the negative pole is divided into two channels. The first channel is output to the negative input terminal of the DC load through the DC contactor and the circuit breaker respectively, and the second channel is connected to the negative input terminal of the battery through the main shunt and the circuit breaker;The DC contactor protects the battery from over-discharge under the control of monitoring; the positive pole of the output of the rectifier module is connected to the positive pole of the load and the positive pole of the battery is connected to the output positive row.

Environmental Conditions

Enviromental parameter Operating environment conditions Transportation environmental conditions Storage environmental conditions Remarks
Project Parameter
Climate conditions Temperature Low temperature -40℃ -40℃ -45℃  -40℃ full load start, + 45~ + 75℃ linear drop
High temperature 45℃ 70℃ 70℃
Humidity Low relative humidity 5% / 5% /
High relative humidity 95% / 95%
Condensation not have / not have
Altitude 4000m 4000m 3000~4000m capacity reduction output
Mechanical stress conditions Vibrate Sinusoidal vibration: Random vibration: / For the plug-in frame only, take out  the rectifier module and monitoring module during testing
5~9Hz: amplitude of  3.5mm; 2~10Hz :30m2/s3;
9~200Hz: Acceleration of  10m/s2; 10~200Hz :3m2/s3;
3 Axial, sweep 5 vibration in each direction 200~500Hz :1m2/s3;
3 Axial, 30min in each direction
Impact (collision) Acceleration of 250m/s2; Acceleration of 400 m/s2; /
Pulse width: 6ms; Pulse width: 6ms;
3 axis 6 to each collision 500 times 3 axis 6 to each collision 500 times
Drop / Drop height of 1m; bottom surface 1 time /
Cooling method Module forced air cooling Wind comes in from the front and comes out from the back

 

System Structure and Layout Drawing:

Embedded Hybrid Power Supply 48V 300A (2)

Technical Parameters:

1.Input characteristics
ON. Project Technical parameter Remarks
1.1 AC input rated voltage Single-phase 220Vac / three-phase 380Vac
1.2  AC-input voltage range 176Vdc~300Vac Full of work
1.3 AC input maximum current 40A 1 phase, the most power supply: 2 modules
1.4 AC input voltage frequency 45~65Hz (Typical value 50 / 60Hz )
1.5 AC power factor ≥0.99 220 Vac rated load
1.6 Pv module input 120Vdc ~ 425Vdc(starting voltage over 160Vdc)
1.7 Pv-rated input voltage 340Vdc
1.8 MPPT voltage range 120Vdc to 340Vdc
1.9 Maximum input current of PV module 17A
1.1 Photovoltaic module reverse pole protection Wrong input polarity, no damage
1.11 Photovoltaic module input insurance Positive and negative insurance
1.12 PV maximum input voltage 450Vdc (Power supply not be damaged)
2. Output characteristics
ON. Project Technical parameter Remarks
2.1 Rectifier output voltage range -43.2Vdc~ -57.6Vdc(typical value-53.5Vdc)
2.2 Recfier output maximum power 18kW
2.3 PV output voltage range -42Vdc~ -58Vdc (typical value-54.5Vdc)
2.4 Voltage stabilization accuracy ≤±1%
2.5 Output ripple & noise ≤200mVp-p Rated input voltage and load and bandwidth limit of 20 MHz
2.6 Current-sharing imbalance ≤±5% Within the 50- -100% load range
2.7 Rectifier module efficiency ≥93% 220 Vac / rated load
2.8 PV module efficiency ≥95% @340/40%~70% Load -54.5Vdc
2.9 Startup time 3~10S The rated input voltage starts to the output voltage establishes to the setting value, the starting output needs to use the pre-flow limit function
2.1 On/off overshoot amplitude ≤±5% When either module is hot plugged (the load current should not be greater than the total output current in the working module), the system output voltage fluctuates
2.11 Dynamic response Overshoot range ≤±5% 25% -50% -25% or 50% -75% -50% load change
Recovery time ≤200µS
2.12 Temperature coefficient ≤±0.02%/℃
2.13 Psophometrically weighted noise voltage ≤2mV
2.14 Wide-band noise   voltage 3.4~150KHz ≤50mV
0.15~30M Hz ≤20mV
2.15 Discrete noise voltage 3.4~150KHz ≤5mV
15~200KHz ≤3mV
20~500KHz ≤2mV
0.5~30M Hz ≤1mV
2.16 Voltage drop ≤500mV
3. Protection characteristics
ON. Project Technical parameter Remarks
3.1 AC input overvoltage protection 300Vdc Can self-recovery, the difference of not less than 10 Vac
3.2 Photovoltaic input overvoltage protection 430Vdc Can self-recovery, the difference of not less than 15 Vac
3.3 AC input undervoltage protection 85Vdc Can self-recover with a return difference of not less than 5 Vac
3.4 Photovoltaic input undervoltage protection 110Vdc Can self-recovery, the difference of not less than 40 Vac
3.5 Recfier output overvoltage protection -59Vdc~-61Vdc Lock, can not recover, need to restart
3.6 Photovoltaic output overvoltage protection Internal-58.5 to-60.5Vdc, external: 63Vdc Lock, can not recover, need to restart
3.7 Output undervoltage protection Battery disconnect protection Through monitoring, the battery can be powered down, and the protection point can be set
3.8 Output limit protection Have
3.9 Output short circuit protection Have Long-term short circuit, can recover from itself
3.1 Overtemperature protection It can recover automatically at the ambient temperature of 75℃
3.11 Battery polarity is connected to reverse protection Not have According to the user needs can have the battery polarity reverse connection protection function
3.12 PV underpower protection  Input power <50W and shutdown for 5 minutes The module starts when the input voltage is greater than 160 Vdc for 5 minutes.

Related products

IP56 Outdoor Industrial UPS 6 10KVA with cabinet air conditioner1
IP56 Outdoor Industrial UPS 6-10KVA with cabinet air conditioner
Three Phase Output Industrial Online UPS 160 300KVA
Three Phase Output Industrial Online UPS 160-300KVA
consnant.com ip55 floor mount outdoor ups 1 10kva with vrla battery1
IP55 floor mount outdoor UPS 1-10KVA with VRLA battery
Three Phase Output Industrial Online UPS 100 120KVA (5)
Three Phase Output Industrial Online UPS 100-120KVA

Related Articles

NEWS 3
Shenzhen CONSNANT Technology Co., Ltd. team building activities Huizhou trip.
NEWS 2
CONSNANT 10th Anniversary Celebration
NEWS 1
CONSNANT Team Building & Annual Meeting Activities

Contact us

Partner with CONSNANT to find the perfect power system for your business. Our technical team is ready to provide customized solutions to optimize power usage and maximize efficiency.

Solution5 1