products

Three Phase Output Industrial Online UPS 160 300KVA

Three Phase Output Industrial Online UPS 160-300KVA

share

Facebook
LinkedIn

Model Number: CNI330 160-300KVA
Nominal Capacity: 160 – 300KVA
Nominal Voltage: 380/400/415VAC
Maximum Input Voltage Range: +-20%
Nominal Frequency: 50/60HZ

Application field:
Power Plant DCS Control System
Boiler Safety Monitoring System
Steam turbine inspection
Bypass systems and other automatic protection devices
Petrochemical, natural gas, plastics, production lines
laboratory testing equipment

Parameter Specification
Item No : CNI330 160-300KVA
Order(MOQ) : 1 pcs
Payment : T/T
Product Origin : China
Color : RAL7035
Shipping Port : Shenzhen
Lead Time : 3-4 weeks
Weight : 1200-2800 Kg

Three Phase Output Industrial Online UPS 160-300KVA

Description

Industrial UPS are regarded as fully customized power supply systems for rugged environments and designed particularly to safeguard critical loads in industrial applications where voltage transients, created by degraded mains supply, can seriously damage both UPS and the critical load.

 

Application:
Petroleum, chemical industry, gas and power station and so on.

 

Key features:
• Adopt full digital control technology.
• Intelligent detection and monitoring function.
• Digitally control the static switch with zero switch.
• Full isolation between input and output.
• Super low output zero earth voltage.
• DC UPS isolated with utility power completely.
• Cubical design with power standard (customization).
• Multifunctional protection for over-voltage, under voltage, over current, short circuit and over temperature and so on.
• Large-screen LCD monitor with Chinese and English operation interface.
• Ultra-long 256 event record, user-friendly analysis and management to the situation of the power supply (touch screen display).
• Static bypass has a strong anti-overload capability.

 

Product advantages:

 

Adopting High-speed DSP Control

Adopting voltage and current stepping technology under CPU control, the rectifier of UPS has a soft start function. The input step is less than 15 seconds (adjustable), and the maximum impact current on the power grid does not exceed the rated current.

 

High Reliability

Built-in input transformer, output transformer, and bypass transformer realize complete Galvanic isolation. Instead of discrete IGBT and SCR components, we uses Modular IGBT and SCR in Rectifier and Inverter, bringing in extremely high reliability.

 

Advanced BMS

Intelligent battery management, comprehensive charge and discharge management of batteries, including charging voltage and current limiting, discharge cut-off voltage, extending battery lifetime 30%-50%.

 

Flexible customization

Industrial UPS can be customized according to the customer’s environment, including input and output voltage, phase, frequency, battery voltage, charging current and IP level of the cabinet, etc.

 

Integrated design

The entire machine adopts a less fuse design, using circuit breakers, contactors, and electronic static switches. The circuit protection technology is advanced, greatly improving the reliability of the entire machine.

 

Strong Impact Ability

Adopting pulse-by-pulse technology to ensure that the maximum short-circuit current does not exceed the allowable range of single pulse short time IGBT, a pulse-by-pulse current limiting scheme is adopted.

 

Suitable for harsh environments

It can be applied in harsh environmental conditions such as dust, pests, high-temperature conditions, and earthquake areas to protect your important production processes and systems.

 

Parallel operation

Advanced distributed active parallel technology can realize parallel operation of 6PCS UPS units without the need for centralized bypass cabinet.

 

High compatibility

Compatible with Lead Acid (vented/sealed), NiCd (vented/gas recombination) batteries and lithium batteries.

 

Production Pictures:

Single Phase Output 60 100KVA Industrial Online UPS (8)

Single Phase Output 60 100KVA Industrial Online UPS (7)

 

Other Service

Service hours: 9:00am-19:00pm (China time)

Product service:
1. Pre-sales consultation; After-sales worry-free.
2. Support ODM and OEM.
3. Online guidance and Technical support.

Product Warranty:
One year warranty period against the B/L date 45 days later.(Possible to extend the warranty period to three years by add money)

FAQ:
We try to answer some frequently asked questions here, if these FAQs don’t answer your questions, please refer to related information from our Product page: Documents Option, which contains Datasheet and Manual for you to download, or you can contact us directly.

What is an uninterruptible power supply system (UPS) and why do I need one?
An uninterruptible power supply (UPS) is an electrical device that provides emergency power to a load when the main power source (typically utility power) fails. It conditions incoming power to ensure clean and uninterrupted power, protects devices from power problems and enables seamless system shutdown during complete outages.
With aging electrical grids, rising power demand, severe weather, faulty wiring and disruptive devices connected to AC lines, equipment is under constant threat from power problems, making a UPS system an important investment. A UPS system is especially useful for networking equipment and other devices that can lose data when power is unexpectedly lost. With a wide range of cost-effective models available, a UPS system is an essential investment to prevent damage, data loss and downtime caused by power problems.
What is the difference between single-phase UPSs vs. three-phase UPSs vs. split-phase UPSs?
Phases of a UPS, such as a single-phase UPS or a three-phase UPS, describe the number of electrical phases that a UPS receives and transmits. Electrical utilities generate three-phase power because that is the most efficient way to transport electricity over long distances. And for larger power consumers, such as large data centers, industrial manufacturing and hospitals, the power stays as three-phase, requiring a three-phase UPS. For smaller power consumers, including residential or office buildings and most K-12 schools, the power is converted to single-phase power.
Some applications contain a mix of single-phase and three-phase equipment and require a UPS that can protect both. For those deployments, a split-phase UPS, which can simultaneously provide 120V and 208V output, is often the best option.
Do UPS systems offer surge and noise protection?
Incorporating built-in surge suppression and noise filtering, uninterruptible power supply (UPS) systems provide comprehensive protection to electronic equipment from transient voltages and electromagnetic/radio frequency interference (EMI/RFI) line noise. This eliminates the need for separate surge protectors, simplifying the setup and saving space. By offering all these features in a single package, a UPS system provides a cost-effective and efficient solution to safeguard valuable equipment from power-related damages.

Technical Parameters:

Model CNI330-160KVA CNI330-200KVA CNI330-300KVA
Capacity 160KVA/128KW 200KVA/160KW 300KVA/240KW
Input
Rated voltage 380/400/415 Vac three-phase
Voltage range ±20%
Frequency range 50/60HZ±5%
Power factor ≥0.8
Current harmonic distortion <5%with harmonic filter
Soft Start 0-100% in 10″
Bypass Input
Rated voltage 380/400/415 Vac single-phase
Permitted voltage range ±15%(selectable from ±10% to±25% from front panel)
Rated frequency 50/60Hz
Permitted frequency range ±2%(selectable from ±1% to 5% from front panel)
Standard features BackFeed portection;split bypass line
Batteries
Type Maintenance-free lead-acid VRLA AGM/GEL;NICd
Maximum recharge current(A) 0.2 X C10
DC Voltage 480VDC
AC ripple voltage <1%
Inverter output
Number of phases 3+N
Rated voltage(V) 380/400/415Vac
Regulation of the output voltage 348~424Vac phase/neutral(from control panel)
Crest factor(Ipeak/Irms) 3:01
Static stability ±1%
Dynamic stability ±5%
Frequency 50/60Hz configurable
Overload 110% 125% 150% of the rated current for 5h/10’/1′
Frequency stability ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present
System
Remote signaling Volt free contacts
Remote controls EPO and Bypass
Communication RS232+romote contacts
Operation temperature 0℃/+40℃
Relative humidity <95% non condensing
Colour Light grey (RAL7035)
Noise 50-65dBA at 1m
Protection degree IP42
Efficiency Smart Mode up to 98%
Compliance Safty: EN 62040-1-1(Directive 2006/95/EC);EMC:6200-2(Directive 2004/108/EC)
Weight(KG)N.W 1428 1902 2800
Dimension W*D*H(mm) 1400*800*1900(2050) 1600*850*1900(2050)
Single Phase Output 60 100KVA Industrial Online UPS (10)

Chemical factory in Kashgar City, Xingjiang

Single Phase Output 60 100KVA Industrial Online UPS (11)

Power Plant in Russia

Single Phase Output 60 100KVA Industrial Online UPS (9)

Shanxi Sinopec

Related products

IP56 Outdoor Industrial UPS 6 10KVA with cabinet air conditioner1
IP56 Outdoor Industrial UPS 6-10KVA with cabinet air conditioner
Three Phase Output Industrial Online UPS 160 300KVA
Three Phase Output Industrial Online UPS 160-300KVA
consnant.com ip55 floor mount outdoor ups 1 10kva with vrla battery1
IP55 floor mount outdoor UPS 1-10KVA with VRLA battery
Three Phase Output Industrial Online UPS 100 120KVA (5)
Three Phase Output Industrial Online UPS 100-120KVA

Related Articles

NEWS 3
Shenzhen CONSNANT Technology Co., Ltd. team building activities Huizhou trip.
NEWS 2
CONSNANT 10th Anniversary Celebration
NEWS 1
CONSNANT Team Building & Annual Meeting Activities

Contact us

Partner with CONSNANT to find the perfect power system for your business. Our technical team is ready to provide customized solutions to optimize power usage and maximize efficiency.

Solution5 1