Model Number: CNH330R 10-40KVA
Nominal Capacity: 10-40KW
Nominal Voltage: 380/400/415VAC
Input Voltage Range: 138~476VAC
Nominal Frequency: 40~70HZ
Description
3-phase 4-wire plus earth input & output design automatically balances three-phase input currents without unbalance risks, perfectly matching medium & large data centers and industrial three-phase power distribution systems.
Adopts Digital Signal Processor (DSP) to boost overall reliability, self-diagnosis, multi-level protection and voltage/frequency regulation performance.
Standard 3U rack size (485×130×728mm), net weight 23–28.5kg per module, enabling high-density cabinet deployment with minimal space occupation.
Supports 30 to 50 pieces of 12V batteries with optional DC voltage from ±180V to ±300Vdc. Max charging current reaches 10A; users can set battery capacity and charging current via dedicated configuration tools.
Automatic smooth switching among three charging phases: high-current constant charge (up to 90% capacity), constant voltage activation & full charging, floating maintenance. This technology accelerates charging and extends battery service life effectively.
Real-time visual monitoring of input/output voltage, frequency, load percentage, battery level and ambient temperature for intuitive daily maintenance.
Standard RS485 communication port; optional SNMP card supports remote monitoring, remote control and fault alarm, compatible with centralized data center management platforms.
Local EPO button and remote REPO interface enable instant full UPS shutdown in emergency scenarios to protect equipment and personnel safety.
Efficiency ≥98% under ECO energy-saving mode and ≥95% under standard online mode. Output voltage precision ±1%; THD ≤2% for linear loads and ≤5% for non-linear loads. Zero transfer time between mains and battery mode.
Ultra-wide input voltage range 138~476VAC, adaptive input frequency 40–70Hz; input power factor ≥0.99 with input current THD ≤3%. Tiered overload protection: 110% load for 60 mins, 125% load for 10 mins, 150% load for 1 min, immediate shutdown above 150% load.
Technical Parameters
|
Model |
CNH330R 10-40KVA | |
|
Capacity |
10-40KVA | |
|
Input |
||
|
Phase |
3Phase/4Wires + Ground |
|
|
Rated Voltage |
380/400/415Vac |
|
|
Voltage Range |
138~476Vac |
|
|
Frequency Range |
40~70Hz |
|
|
Power Factor |
≥0.99 |
|
|
Bypass Voltage Range |
Max.voltage: +15%(optional +5%、+10%、+25% ) Min. voltage: -45% (optional -20%、-30%) Frequency protection range: ±10% |
|
|
Current Harmonic |
≤3(100% linear load) |
|
|
Output |
||
|
Phase |
3Phase/4Wires + Ground |
|
|
Rated Voltage |
380/400/415Vac |
|
|
Power Factor |
0.9 |
|
|
Voltage Precision |
±1% |
|
|
Output Frequency |
Utility Mode |
±1%、±2%、±4%、±5%、±10% of the rated frequency(optional) |
|
Battery Mode |
(50/60±0.2)Hz |
|
|
Crest Factor |
3:1 |
|
|
Transfer Time |
Utility to Battery : 0ms Utility to bypass : 0ms (following) |
|
|
Overload Capacity |
Load≤110%,60min,≤125%,last 10min,≤150%last 1min,≥150% shut down UPS immediately |
|
|
THD |
≤2% with linear load |
|
|
Efficiency |
ECO mode≥98%;Normal mode≥95% |
|
|
Comunication Interface |
||
|
UPS module |
RS485、SNMP card(optional) |
|
|
Battery |
||
|
Voltage |
±180V/±192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc optional |
|
|
Charge Current(A):UPS module |
Maximum current 10A |
|
|
Backup time |
Depends on the capacity of external batteries |
|
|
Operating Environment |
||
|
Temperature |
0℃~40℃ |
|
|
Humidity |
0~95% non condensing |
|
|
Storage temperature |
-25℃~55℃ |
|
|
Altitude |
< 1500m |
|
|
Other |
||
|
Unit Dimensions(W*H*D) |
485×130 x728mm |
|
|
Weight (Kg) |
23/25/25/26/28.5 |
|
|
Industry Standard |
CE,EN/IEC 62040-2,EN/IEC 62040-1-1 |
|
Partner with CONSNANT to find the perfect power system for your business. Our technical team is ready to provide customized solutions to optimize power usage and maximize efficiency.