Model Number: OD-TRSS-48300/OD-TRSS-48600
Input AC voltage range:176Vdc~300Vac
Output DC voltage range: -43.2Vdc~ -57.6Vdc (Typical value-53.5Vdc)
Storage temperature Range: -45℃~+70℃
Application field:
Communication Base Station
Description
OD-TRSS series is an integrated outdoor hybrid energy telecom power system independently developed by CONSNANT, combining high-efficiency AC rectifier modules and multi-channel MPPT solar charge modules, delivering standard -48VDC power supply for telecom equipment.
Designed for mains + photovoltaic complementary power supply, the system realizes solar priority energy dispatch to maximize solar utilization and cut site electricity expenditure. It supports seamless coordination of mains grid, PV panels, storage batteries and optional diesel generator, ensuring zero-interruption power supply for remote communication sites with unstable power or no grid coverage. The whole machine adopts IP55 outdoor cabinet structure with compact layout, front access maintenance, and optional air conditioner/electric heater to adapt to extreme outdoor environments.
Working Principle:
Under normal grid power, rectifier modules, MPPT solar modules, load equipment and batteries operate in parallel floating charging mode. Solar power supplies loads and charges batteries preferentially; when solar output is insufficient, rectifiers automatically supplement power.
1. Mains outage with normal PV output: Solar modules feed loads and charge batteries.
2. Mains outage + PV failure: Batteries discharge to sustain loads. When battery voltage drops to generator startup threshold, the monitoring unit sends startup signal to diesel generator; the generator supplies AC to rectifiers to recharge batteries and restore full load power. When battery voltage reaches generator stop threshold, the system shuts down the generator automatically.
Core Features:
1. High-Performance Hot-Swap Power Modules
◦ MPPT solar tracking accuracy ≥99.5%, solar module efficiency ≥95%; rectifier with active PFC (PF≥0.99), peak efficiency ≥93%~96%.
◦ Non-destructive plug-and-play hot swap for rectifier & PV modules; module replacement finished within 1 minute without system shutdown.
◦ Dual hardware + software overvoltage protection; software OVP supports two lockout modes for selection.
◦ High power density, 1–6 modules for 300A model, 1–12 modules for 600A model for flexible capacity expansion.
2. Intelligent Battery Management System
Full battery protection suite, automatic voltage regulation, stepless current limiting, real-time battery capacity calculation, auto float/equal charge switching, online battery health test function.
3. Optimal Solar-Grid Complementary Control
Intelligent energy management logic prioritizes PV power output to loads, fully exploits renewable energy to reduce grid consumption and carbon emissions.
4. Complete Data Statistics & Historical Recording
Real-time statistics of load power consumption, PV generation, mains power input, diesel generator output, battery charge/discharge volume; stores 90-day historical operation data, 200 fault alarm records and 10 groups of battery test data, all data remotely uploadable.
5. Comprehensive Alarm & Multi-Layer Protection
Full-range electrical protection: AC over/undervoltage, PV over/undervoltage, output OVP/UVP, overcurrent, short-circuit, over-temperature, PV reverse polarity protection; built-in AC & DC two-stage lightning protection SPD for thunderstorm-prone regions.
6. Humanized Monitoring & Remote Management
15° inclined LCD operation panel for intuitive parameter query, historical alarm check and manual system control; supports dry contact alarm, RS485 communication, optional GPRS modem for cloud remote monitoring and unattended site operation; local software upgrade available.
7. Advanced Energy-Saving Design
Rectifier automatic sleep function under light load, dual steady-state contactors, low-power shunt and variable-speed fan technology to lower standby power loss.
8. Rugged Outdoor Cabinet Design
IP55 dustproof & waterproof rating, RAL7035 standard cabinet color; wide operating temperature range (-40℃~+50℃ for 300A model, -15℃~+45℃ for 600A model), storage temperature -45℃~+70℃; works stably up to 4000m altitude (derated output above 3000m). Optional AC heater for low-temperature reliable startup.
9. Stable Electrical Output Performance
Wide AC input 176~300VAC (45–65Hz), PV input 120–425VDC; output DC range -43.2~-57.6VDC (typical -53.5VDC); tight voltage stabilization accuracy ≤±1%, low ripple noise, fast dynamic load response, balanced current sharing among parallel modules.
Technical Specifications:
| Model | OD-TRSS-48300 | OD-TRSS-48600 |
|
| Cabinet | Size(mm) | W*D*H=759*693*1430(without air-conditioner)
W*D*H=759*817*1430(with air-conditioner) |
W*D*H=759*693*1430(without air-conditioner)
W*D*H=759*817*1430(with air-conditioner) |
| User equipment space(U) | Height: 17U; Width: 15U | Height: 15U; Width: 15U | |
| Weight (kg) | N.W :130 kg | N.W :160 kg | |
| Rectifier module | Number (pcs) | 1-6 pcs(Optional) | 1-12 pcs(Optional) |
| Size(mm) | Individual module: W*D*H=106.5*286*41.5(±0.5mm) | ||
| Weight (kg) | < 1.75 kg (Individual module) | ||
| Solar MPPT module
|
Number (pcs) | 1-6pcs(Optional) | 1-12 pcs(Optional) |
| Size(mm) | Individual module: W*D*H=106.5*286*41.5(±0.5mm) | ||
| Weight (kg) | < 1.75 kg (Individual module) | ||
| AC Input characteristics | |||
| AC input rated voltage | Single-phase 220Vac / three-phase 380Vac | Single-phase 220Vac / three-phase 380Vac | |
| AC-input voltage range | 176Vdc~300Vac (Full of work) | 176Vdc~300Vac (176-275Vac@ system output rated capacity.) | |
| AC input maximum current | 40A (1 phase, the most power supply: 2 modules) | 80A (One phase can control up to 4 modules) | |
| AC input voltage frequency | 45~65Hz (Typical value 50 / 60Hz ) | ||
| AC power factor | ≥0.99 (220 Vac rated load) | ||
| Input current harmonics | ≤3% (220 Vac) | ||
| Midline current | <30% phase line current (In three-phase balanced system) | ||
| PV Input characteristics | |||
| Pv module input | 120Vdc ~ 425Vdc (Starting voltage over 160Vdc) | ||
| Pv-rated input voltage | 340Vdc | ||
| MPPT voltage range | 120Vdc to 340Vdc | ||
| Maximum input current of PV module | 17A | ||
| Photovoltaic module reverse pole protection | Wrong input polarity, no damage | ||
| Photovoltaic module input protection | Positive and negative insurance | ||
| PV maximum input voltage | 450Vdc (Power supply not be damaged) | ||
| Output characteristics | |||
| Rectifier output voltage range | -43.2Vdc~ -57.6Vdc (Typical value-53.5Vdc) | ||
| Rectifier output maximum power | 18kW | 36kW | |
| PV output voltage range | -42Vdc~ -58Vdc (Typical value-54.5Vdc) | ||
| Voltage stabilization accuracy | ≤±1% | ||
| Output ripple & noise | ≤200mVp-p (Rated input voltage and load and bandwidth limit of 20 MHz) | ≤100mVp-p (Rated input voltage and load and bandwidth limit of 20 MHz) | |
| Current-sharing imbalance | ≤±5% (Within the 50- -100% load range) | ≤±3% (Within the 50- -100% load range and when there is no monitoring, the modules can autonomously share current.) | |
| Rectifier module efficiency | ≥93% ,≥95%,≥96% (220 Vac / rated load) | ≥94% (220Vac/100% load rate) | |
| PV module efficiency | ≥96% | ||
| Startup time | 3~10S (The rated input voltage starts to the output voltage establishes to the setting value, the starting output needs to use the pre-flow limit function) | ||
| On/off overshoot amplitude | ≤±5% (When either module is hot plugged (the load current should not be greater than the total output current in the working module), the system output voltage fluctuates) | ≤±3% (When either module is hot plugged (the load current should not be greater than the total output current in the working module), the system output voltage fluctuates) | |
| Dynamic response
|
Overshoot range | ≤±5% (25% -50% -25% or 50% -75% -50% load change) | ≤±1% (25% -50% -25% or 50% -75% -50% load change) |
| Recovery time | ≤200µS (25% -50% -25% or 50% -75% -50% load change) | ≤10µS (25% -50% -25% or 50% -75% -50% load change) | |
| Temperature coefficient | ≤±0.02%/℃ | ≤±0.02%/℃ (The difference between the DC output voltage and the output voltage setting value when the temperature changes by 10°C should not exceed ±0.02% of the output voltage setting value.) | |
| Psophometrically weighted noise voltage | ≤2mV | ||
| Wide-band noise voltage
|
3.4~150KHz | ≤50mV | ≤3mV |
| 0.15~30MHz | ≤20 | ≤5mV | |
| Discrete noise voltage
|
3.4~150KHz | ≤5mV | ≤2mV |
| 150~200KHz | ≤3mV | ≤1mV | |
| 200~500KHz | ≤2mV | ≤1mV | |
| 0.5~30MHz | ≤1mV | ≤1mV | |
| Voltage drop | ≤500mV | ||
| Protection characteristics | |||
| AC input overvoltage protection | 300Vdc (Can self-recovery, the difference of not less than 10 Vac) | ||
| AC input undervoltage protection | 85Vdc (Can self-recover with a return difference of not less than 5 Vac) | 80Vdc (Can self-recover with a return difference of not less than 5 Vac) | |
| Photovoltaic input overvoltage protection | 430Vdc (Can self-recovery, the difference of not less than 15 Vac) | ||
| Photovoltaic input undervoltage protection | 110Vdc (Can self-recovery, the difference of not less than 40 Vac) | ||
| Rectifier output overvoltage protection | -59Vdc~-61Vdc (Lock, can not recover, need to restart) | -58.5Vdc~-60.5Vdc (Locked) | |
| Photovoltaic output overvoltage protection | Internal-58.5 to-60.5Vdc, External: 63Vdc (Lock, can not recover, need to restart) | ||
| Output undervoltage protection | Battery disconnect protection (Through monitoring, the battery can be powered down, and the protection point can be set) | ||
| Output limit protection | Have | Have (Output current limiting range: adjusted between 20% and 110% of the nominal current value) | |
| Output short circuit protection | Have (Long-term short circuit, can recover from itself) | ||
| Overtemperature protection | It can recover automatically at the ambient temperature of 75℃. | It can recover automatically at the ambient temperature of 65℃. | |
| Battery polarity is connected to reverse protection | Not have (According to the user needs can have the battery polarity reverse connection protection function) | ||
| Battery manual power-off protection | Not have | ||
| PV underpower protection | Input power <50W and shutdown for 5 minutes (The module starts when the input voltage is greater than 160 Vdc for 5 minutes.) | ||
| Environmental | |||
| Operating temperature | -40℃-50℃ | -15℃-45℃ | |
| Storage temperature | -45℃-70℃ | -40℃-70℃ | |
| Relative humidity | 5%-95% | ||
| Altitude(m) | ≤4000m (3000~4000m capacity derated output) | ||